Watermark Granular Matrix sensors are available from Irrometer Company, Riverside CA 951/689-1701 <http://www.irrometer.com/agcat.htm#watermark>. These "granular matrix" devices consist of a fine aggregate mixed with a gypsum buffer, held inside a permeable membrane and a perforated stainless steel sleeve. This device is buried in intimate contact with soil, and reaches an equilibrium with the soil moisture. Electrodes are embedded in the granular matrix, and the the electrical conductance between them is the parameter measured. Conductance increases with increasing soil moisture (and also depends on temperature,which can be compensated). The purpose of the gypsum is to buffer the measurement from ions that are found in uncontrolled amounts in the soil. Solid gypsum block sensors are similar, electrodes embedded in a gypsum block with proprietary additives and controlled manufacturing processes. The Watermark formulation claims to have a wider range of response and a longer field life and is especially suited for the range of soil moisture typically encountered in agriculture. The gypsum block sensor may offer extended range at the dry end of the scale.
The bottom line is that the sensor may be used as a tool to
optimize irrigation and to warn of plant stress. The sensor reading is
resistance in Ohms, but that may be translated by calculation or by a
table to a value in
kilo-Pascal (kPa, same as centi-bar). For best
results, the calibration should be carried out in the soil type to be
monitored.
A special circuit is needed to measure the electrical resistance of the Watermark or gypsum block sensors. Continuous DC currents must not be allowed to flow through the wet part of the circuit, or else irreversible reactions occur on the metal surface that spoil the readings. AC excitation avoids these problems, by reversing the polarity of the current many times per second, so that no net reaction takes place at either electrode.
A related issue is galvanic currents. If two devices are immersed in the same environment (say two moisture sensors near each other in the soil), or a ground connection to a data logger can generate "ground loop" voltages and currents. The coupling effect between the two sensors or any other conductive path both degrades the reading and exacerbates corrosion. It is important to avoid DC "sneak" paths between different sensors. The same consideration applies to other objects in the environment: Metal tanks, ground rods, salinity gradients. Any or all of these can contribute to underwater potential differences that are continually driving current through the wet medium, and through sensors immersed in the medium.
The SMX circuit provides the AC excitation and galvanic isolation
required. The output signal is a frequency, or alternatively a
current or a voltage, that depends in a relatively simple manner on
the resistance of the sensor. Two wires connect to the watermark
sensor, and the other wires produce the voltage, current or frequency
signal that is routed to a data logger or controller. In addition
to its intended use with the Watermark sensor, the SMX has found more
unusual applications from airplane wing deicer bags to baby diaper
monitors, using specially designed sensor electrodes.
Specifications:
PRICE:
|
![]() left: encapsulated module ---------------- right: core PCB
|
Attach the Watermark sensor to the pair of blue wires. The polarity does not matter. (Please consult EME Systems if you are located in an area where there is lightning. The soil moisture sensor is intrinsically grounded at the point where it is buried. If there is a long cable between the sensor and your equipment, or if the equipment is itself connected to a different ground point, you must add a zap protection circuit to the SMX where it connects to the probe, and make careful consideration of the ground loop.)
Figure 1 shows how to connect the sensor for digital frequency output. The resistor (10kohms, value not critical) can pull up to any voltage from 3 to 7 volts dc. The output signal then is a square wave, and its frequency varies from 50 hz when the sensor is bone dry, up to 10000+ hertz when the sensor is soaking wet. This output can be measured using a COUNT or PERIOD function on the data logger. Note that the white and the black wires are connected together.
Figure 1: connection for 50hz to 10,000 hz frequency output
Figure 2 shows how to connect the sensor for voltage output. The green wire is not used and should be connected to the white wire (not the black wire!). The output signal is a voltage that varies from <0.2 volts when the sensor is bone dry, up to over 1 volt when the sensor is soaking wet.
Figure 2: connection for voltage
Figure 3 shows how to connect the sensor for two wire current output. The black wire should be connected to the white wire. The output signal is a current that varies from 0.2 milliamp when the sensor is bone dry, up to over 1 milliamp when the sensor is soaking wet. The current on the two wire circuit may be converted to a voltage at the input of the data logger. A 1 k½ resistor will convert the 0.2 to 1.0 millamp current into a 0.2 to 1 volt signal. The power supply voltage must be a high enough voltage to maintain the 4 volts required by the SMX module itself.
Figure 3: connection for current
|
(green wire) |
(white & blackwire) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|


The Irrometer web site <http://www.irrometer.com/agcat.htm#watermark> offers links to a number of agricultural engineering publications that evaluate the Watermark sensor. Here are additional links:
- Sowacs
- The main clearinghouse for all aspects and techniques of soil moisture measurement
- Sowacs mail archive
- The mail list covers a wide range of questions and answers. Moderated by Bruce Metelerkamp.
- Resurrecting the Gypsum Block for Soil Moisture Measurement
- Sowacs-mea-gypsum block email
- Measurement Engineering Australia - Environmental Monitoring Systems
- Articles by Andrew Skinner of Measurement Engineering Australia (MEA), and a link to the company web site.
- Irrometer
- Manufacturer of the Watermark sensor, corporate web site
- GMS Malheur OSU - Clinton Shock
- Malheur experiment station at Oregon State University, bibliography of experimental research
- Watermark calibration
- Soil Water Management
- Watermark to HOBO data logger
- Articles from Rick Allen at the University of Idaho
- UArizona/GLOBE Soil Moisture Project
- University of Arizona educational project on parameters of global environmental importance
- Delmhorst Instrument Company
- Soil Moisture Corporation
- Manufacturers of soil moisture sensors and equipment
- Remote Measurement Systems - Sensors and Techniques
- Another conductance-->voltage converter.